Electrical / Free calculator
Voltage drop and wire size
Estimate voltage drop for a chosen conductor, or find the smallest listed size meeting your drop target.
Type into any number field to pin it. Calculated fields carry a rust-colored rule. Clear a pin to let it solve again. Starting values are editable assumptions, not measured facts.
Your numbers
Verify all units and results for your own use.
Your results
Your worksheet
Download or copy the complete entered and calculated values without giving us an email address.
Read or copy the worksheet
Email is optional.
Full results and the worksheet are free above. Each button requests only the extra it names. No other list is bundled in.
Notification signup sends your email address and the notification you choose to Buttondown. Check your inbox to confirm. Worksheet and saved-link email delivery remain disabled.
Technical notes and factor sources
Factors as of: Source pages reviewed 2026-10-31; Cerrowire table edition not stated
Review date: 2026-10-31 (build review, not engineering signoff)
Resistance-only approximation at 75 C. It ignores reactance, AC power factor, parallel conductors, harmonics and actual conductor temperature. The automatic selection is the smallest SOURCED size meeting voltage drop only. It does not establish ampacity, overcurrent protection, terminal suitability, installation safety or NEC compliance. The tool sizes nothing for an actual installation.
Declared relations
- dropArea = 1 x drop x area
- dropArea = 1 x amps x length x selected source coefficient (see notes)
- drop = 0.01 x voltage x dropPercent
- Smallest sourced area satisfying the selected target; candidates from wireSizes
- 1 x area = 0
All fields solve from the declared relations in either direction when a unique value exists. Calculated values use full precision. Conflicts use a relative tolerance of 0.01%, with an absolute floor of 0.000001. Zero divided by zero has no unique solution. A cleared field can be calculated again when other entries determine it.
Single-phase drop = 2 x K x amps x one-way feet / circular mils. Three-phase uses 1.732 instead of 2.
Drop percent = 100 x drop / source voltage. Automatic size requires voltage, amps, one-way length and a positive target.
3% branch and 5% total are common NEC informational-note guidance, not universal code requirements. Local requirements and project specifications can differ.
Only listed standard sizes are searched; no extrapolation above 500 kcmil or unlisted intermediate size. Check ampacity separately.
constants / sourced values
- Reference constant
- 3 percent branch-circuit reference. Source: NEC 210.19(A) informational-note guidance as described by PowersYourTeam. Factors as of 2026-10-31; review 2026-10-31.
- Reference constant
- 5 percent combined feeder and branch reference. Source: NEC 215.2(A) informational-note guidance as described by PowersYourTeam. Factors as of 2026-10-31; review 2026-10-31.
- Reference constant
- 1.732 dimensionless three-phase multiplier (rounded square root of 3). Source: Declared balanced three-phase model. Factors as of 2026-10-31; review 2026-10-31.
materials / sourced values
- Copper
- 12.9 ohm-circular mil/ft at 75 C. Source: PowersYourTeam published K values. Factors as of 2026-10-31; review 2026-10-31.
- Aluminum
- 21.2 ohm-circular mil/ft at 75 C. Source: PowersYourTeam published K values. Factors as of 2026-10-31; review 2026-10-31.
wireSizes / sourced values
- 14 AWG
- 4110 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 12 AWG
- 6530 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 10 AWG
- 10380 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 8 AWG
- 16510 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 6 AWG
- 26240 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 4 AWG
- 41740 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 3 AWG
- 52620 circular mils. Source: Southwire SPEC 10080, 3 AWG area. Factors as of 2026-10-31 source snapshot; review 2026-10-31.
- 2 AWG
- 66360 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 1 AWG
- 83690 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 1/0 AWG
- 105600 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 2/0 AWG
- 133100 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 3/0 AWG
- 167800 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 4/0 AWG
- 211600 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 250 kcmil
- 250000 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 300 kcmil
- 300000 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 350 kcmil
- 350000 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
- 500 kcmil
- 500000 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
Sources by name
- Cerrowire Ampacity Charts: NEC Table 310.16 public reproduction
- Paige Water: Wire Size Conversion, circular-mil areas
- PowersYourTeam: published 75 C K values and voltage-drop formulas
- Paige Electric: Wire Resistance and Properties; source noted as 2008 NEC
- Southwire SPEC 10080: 3 AWG area 52620 circular mils
Results are estimates for planning. Permit and engineering decisions need a qualified professional.
Keep the tools on your phone.
iPhone: open this page in Safari, tap Share, then Add to Home Screen. Android: use Chrome's Install app or Add to Home screen menu.
Preparing offline tools. Keep this page open until they are ready.
Your numbers stay in this browser on this device. Browser cleanup can remove them. We do not use cookies or send your numbers to a server.