Electrical / Free calculator

Ampacity and electrical power

Look up a sourced base ampacity, then work between volts, amps, power factor, kW and kVA.

Type into any number field to pin it. Calculated fields carry a rust-colored rule. Clear a pin to let it solve again. Starting values are editable assumptions, not measured facts.

Your numbers

Verify all units and results for your own use.

Your results

Your worksheet

Download or copy the complete entered and calculated values without giving us an email address.

Read or copy the worksheet

Email is optional.

Full results and the worksheet are free above. Each button requests only the extra it names. No other list is bundled in.

Notification signup sends your email address and the notification you choose to Buttondown. Check your inbox to confirm. Worksheet and saved-link email delivery remain disabled.

Technical notes and factor sources

Factors as of: Source pages reviewed 2026-10-31; Cerrowire table edition not stated
Review date: 2026-10-31 (build review, not engineering signoff)

Base table ampacity only, at 30 C ambient with no more than three current-carrying conductors. Missing source cells are not interpolated: aluminum 60 C has no values loaded; copper 60 C is limited to 14 through 2 AWG. Adjust for ambient temperature, conductor count and installation conditions. Terminal ratings may govern, often at 75 C, and some equipment requires 60 C. Small-conductor overcurrent limits and continuous-load rules are separate. This page selects no breaker and approves no installation.

Declared relations

  • kva = 0.001 x voltage x amps x selected source coefficient (see notes)
  • kw = 1 x kva x pf
  • 1 x tableAmps = 0

All fields solve from the declared relations in either direction when a unique value exists. Calculated values use full precision. Conflicts use a relative tolerance of 0.01%, with an absolute floor of 0.000001. Zero divided by zero has no unique solution. A cleared field can be calculated again when other entries determine it.

Balanced single-phase real power: kW = V x A x PF / 1000. Balanced three-phase uses line-to-line voltage and line current: kW = 1.732 x V x A x PF / 1000.

kVA uses the same voltage/current expression without power factor. kW = kVA x PF. PF is a ratio from 0 to 1, not a percent.

The lookup returns a table ampacity; it does not force your entered current to equal that value. Enter current independently for power calculations.

Public source gaps remain blank. A wire appears in the lookup dropdown only when its material/temperature cell is sourced. NEC as adopted locally and the authority having jurisdiction control.

The 6 AWG aluminum 90 C cell is withheld: the chosen public reproduction shows 55 A, inconsistent with common Table 310.16 reproductions. It is not substituted with an unsourced value.

materials / sourced values
Copper
12.9 ohm-circular mil/ft at 75 C. Source: PowersYourTeam published K values. Factors as of 2026-10-31; review 2026-10-31.
Aluminum
21.2 ohm-circular mil/ft at 75 C. Source: PowersYourTeam published K values. Factors as of 2026-10-31; review 2026-10-31.
wireSizes / sourced values
14 AWG
4110 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
12 AWG
6530 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
10 AWG
10380 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
8 AWG
16510 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
6 AWG
26240 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
4 AWG
41740 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
3 AWG
52620 circular mils. Source: Southwire SPEC 10080, 3 AWG area. Factors as of 2026-10-31 source snapshot; review 2026-10-31.
2 AWG
66360 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
1 AWG
83690 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
1/0 AWG
105600 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
2/0 AWG
133100 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
3/0 AWG
167800 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
4/0 AWG
211600 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
250 kcmil
250000 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
300 kcmil
300000 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
350 kcmil
350000 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
500 kcmil
500000 circular mils. Source: Paige Electric Wire Resistance and Properties, 2008 NEC-based table. Factors as of 2008 table; source snapshot 2026-10-31; review 2026-10-31.
Sourced base ampacity cells
SizeMaterial / columnBase A
14copper / 60 C15
14copper / 75 C20
14copper / 90 C25
12copper / 60 C20
12copper / 75 C25
12copper / 90 C30
12aluminum / 75 C20
12aluminum / 90 C25
10copper / 60 C30
10copper / 75 C35
10copper / 90 C40
10aluminum / 75 C30
10aluminum / 90 C35
8copper / 60 C40
8copper / 75 C50
8copper / 90 C55
8aluminum / 75 C40
8aluminum / 90 C45
6copper / 60 C55
6copper / 75 C65
6copper / 90 C75
6aluminum / 75 C50
4copper / 60 C70
4copper / 75 C85
4copper / 90 C95
4aluminum / 75 C65
4aluminum / 90 C75
3copper / 60 C85
3copper / 75 C100
3copper / 90 C115
3aluminum / 75 C75
3aluminum / 90 C85
2copper / 60 C95
2copper / 75 C115
2copper / 90 C130
2aluminum / 75 C90
2aluminum / 90 C100
1copper / 75 C130
1copper / 90 C145
1aluminum / 75 C100
1aluminum / 90 C115
1/0copper / 75 C150
1/0copper / 90 C170
1/0aluminum / 75 C120
1/0aluminum / 90 C135
2/0copper / 75 C175
2/0copper / 90 C195
2/0aluminum / 75 C135
2/0aluminum / 90 C150
3/0copper / 75 C200
3/0copper / 90 C225
3/0aluminum / 75 C155
3/0aluminum / 90 C175
4/0copper / 75 C230
4/0copper / 90 C260
4/0aluminum / 75 C180
4/0aluminum / 90 C205
250copper / 75 C255
250copper / 90 C290
250aluminum / 75 C205
250aluminum / 90 C230
300copper / 75 C285
300copper / 90 C320
300aluminum / 75 C230
300aluminum / 90 C260
350copper / 75 C310
350copper / 90 C350
350aluminum / 75 C250
350aluminum / 90 C280
500copper / 75 C380
500copper / 90 C430
500aluminum / 75 C310
500aluminum / 90 C350

Sources by name

  1. Cerrowire Ampacity Charts: NEC Table 310.16 public reproduction
  2. Paige Water: Wire Size Conversion, circular-mil areas
  3. PowersYourTeam: published 75 C K values and voltage-drop formulas
  4. Paige Electric: Wire Resistance and Properties; source noted as 2008 NEC
  5. Southwire SPEC 10080: 3 AWG area 52620 circular mils

Results are estimates for planning. Permit and engineering decisions need a qualified professional.

Keep the tools on your phone.

iPhone: open this page in Safari, tap Share, then Add to Home Screen. Android: use Chrome's Install app or Add to Home screen menu.

Preparing offline tools. Keep this page open until they are ready.

Your numbers stay in this browser on this device. Browser cleanup can remove them. We do not use cookies or send your numbers to a server.